Normional cross-sectional area of conductor mm2 | Normal thickness of insulation mm | Normal thickness of sheath mm | Outer diameter of cable mm | Calculated weight of cable Kg/km | Current rating A | |
Min | Max | |||||
1.5 | 0.8 | 1.4 | 5.6 | 7.2 | 62 | 29 |
2.5 | 0.9 | 1.4 | 6.4 | 8.0 | 85 | 37 |
4 | 1.0 | 1.5 | 7.2 | 9.0 | 114 | 47 |
6 | 1.0 | 1.6 | 8 | 11.0 | 148 | 52 |
10 | 1.2 | 1.8 | 9.8 | 13.0 | 227 | 75 |
16 | 1.2 | 1.9 | 11 | 14.5 | 305 | 112 |
25 | 1.4 | 2.0 | 12.5 | 16.5 | 446 | 148 |
35 | 1.4 | 2.2 | 14 | 18.5 | 595 | 183 |
50 | 1.6 | 2.4 | 16.5 | 21.0 | 799 | 226 |
70 | 1.6 | 2.6 | 18.5 | 24.0 | 1060 | 289 |
95 | 1.8 | 2.8 | 21 | 26.0 | 1401 | 353 |
120 | 1.8 | 3.0 | 23 | 28.5 | 1667 | 415 |
150 | 2.0 | 3.2 | 25 | 32.0 | 2034 | 460 |
185 | 2.2 | 3.4 | 27.5 | 34.5 | 2524 | 529 |
240 | 2.4 | 3.5 | 30.5 | 38.0 | 3195 | 636 |
300 | 2.6 | 3.6 | 33.5 | 41.5 | 3901 | 732 |
400 | 2.8 | 3.8 | 37.5 | 46.5 | 5095 | 877 |
Normional cross-sectional area of conductor mm2 | Normal thickness of insulation mm | Normal thickness of sheath mm | Outer diameter of cable mm | Calculated weight of cable Kg/km | Current rating A | |
Min | Max | |||||
2×1.5 | 0.8 | 1.5 | 9.0 | 11.5 | 147 | 21 |
2×2.5 | 0.9 | 1.7 | 10.5 | 13.5 | 232 | 30 |
2×4 | 1.0 | 1.8 | 12.0 | 15.0 | 308 | 39 |
2×6 | 1.0 | 2.0 | 13.5 | 18.5 | 409 | 57 |
2×10 | 1.2 | 3.1 | 18.5 | 24.0 | 737 | 74 |
2×16 | 1.2 | 3.3 | 21.0 | 27.5 | 965 | 98 |
2×25 | 1.4 | 3.6 | 24.5 | 31.5 | 1444 | 135 |
2×35 | 1.4 | 3.9 | 27.5 | 35.5 | 1875 | 167 |
2×50 | 1.6 | 4.3 | 32.0 | 41.0 | 2536 | 208 |
2×70 | 1.6 | 4.6 | 36.0 | 46.0 | 3257 | 259 |
2×95 | 1.8 | 5.0 | 40.5 | 50.5 | 4349 | 318 |
Normional cross-sectional area of conductor mm2 | Normal thickness of insulation mm | Normal thickness of sheath mm | Outer diameter of cable mm | Calculated weight of cable Kg/km | Current rating A | |
Min | Max | |||||
3×1.5 | 0.8 | 1.6 | 9.6 | 12.5 | 178 | 19 |
3×2.5 | 0.9 | 1.8 | 11.5 | 14.5 | 276 | 26 |
3×4 | 1.0 | 1.9 | 13.0 | 16.0 | 374 | 34 |
3×6 | 1.0 | 2.1 | 14.5 | 20.5 | 499 | 43 |
3×10 | 1.2 | 3.3 | 20.0 | 25.5 | 898 | 63 |
3×16 | 1.2 | 3.5 | 22.5 | 29.5 | 1191 | 84 |
3×25 | 1.4 | 3.8 | 26.5 | 34.0 | 1780 | 115 |
3×35 | 1.4 | 4.1 | 29.5 | 38.0 | 2330 | 142 |
3×50 | 1.6 | 4.5 | 34.5 | 43.5 | 3054 | 176 |
3×70 | 1.6 | 4.8 | 38.5 | 49.5 | 4095 | 224 |
3×95 | 1.8 | 5.3 | 44.0 | 54.0 | 5481 | 273 |
3×120 | 1.8 | 5.6 | 48.0 | 59.0 | 6459 | 316 |
3×150 | 2.0 | 6.0 | 53.0 | 66.5 | 7797 | 454 |
Normional cross-sectional area of conductor mm2 | Normal thickness of insulation mm | Normal thickness of sheath mm | Outer diameter of cable mm | Calculated weight of cable Kg/km | Current rating A | |
Min | Max | |||||
4×1.5 | 0.8 | 1.7 | 10.5 | 13.5 | 219 | 19 |
4×2.5 | 0.9 | 1.9 | 12.5 | 15.5 | 341 | 26 |
4×4 | 1.0 | 2.0 | 14.5 | 18.0 | 464 | 34 |
4×6 | 1.0 | 2.3 | 21.5 | 22.0 | 627 | 43 |
4×10 | 1.2 | 3.4 | 24.5 | 28.0 | 1101 | 63 |
4×16 | 1.2 | 3.6 | 29.5 | 32.0 | 1471 | 84 |
4×25 | 1.4 | 4.1 | 33.0 | 37.5 | 2244 | 115 |
4×35 | 1.4 | 4.4 | 38.0 | 42.0 | 2942 | 142 |
4×50 | 1.6 | 4.8 | 43.0 | 48.5 | 3971 | 176 |
4×70 | 1.6 | 5.2 | 49.0 | 55.0 | 5210 | 224 |
4×95 | 1.8 | 5.9 | 44.0 | 60.5 | 7024 | 273 |
4×120 | 1.8 | 6.0 | 53.0 | 65.5 | 8213 | 316 |
4×150 | 2.0 | 6.5 | 59.0 | 74.0 | 10042 | 454 |
Normional cross-sectional area of conductor mm2 | Normal thickness of insulation mm | Normal thickness of sheath mm | Outer diameter of cable mm | Calculated weight of cable Kg/km | Current rating A | |
Min | Max | |||||
5×1.5 | 0.8 | 1.8 | 11.5 | 15.0 | 268 | 19 |
5×2.5 | 0.9 | 2.0 | 13.5 | 17.0 | 416 | 26 |
5×4 | 1.0 | 2.2 | 16.0 | 19.5 | 576 | 34 |
5×6 | 1.0 | 2.5 | 18.0 | 24.5 | 781 | 43 |
5×10 | 1.2 | 3.6 | 24.0 | 31.0 | 1346 | 63 |
5×16 | 1.2 | 3.9 | 27.0 | 35.5 | 1818 | 84 |
5×25 | 1.4 | 4.4 | 32.5 | 41.5 | 2765 | 115 |
Normional cross-sectional area of conductor mm2 | Normal thickness of insulation mm | Normal thickness of sheath mm | Outer diameter of cable mm | Calculated weight of cable Kg/km | Current rating A | |||
Master Core | Neutral core | Master Core | Neutral core | Min | Max | |||
3×2.5 | 1.5 | 0.9 | 0.8 | 2.0 | 12.5 | 15.5 | 321 | 26 |
3×4 | 2.5 | 1.0 | 0.9 | 2.0 | 14.5 | 17.5 | 434 | 34 |
3×6 | 4 | 1.0 | 1.0 | 2.2 | 16.0 | 21.0 | 585 | 43 |
3×10 | 6 | 1.2 | 10 | 3.0 | 20.5 | 26.5 | 966 | 63 |
3×16 | 6 | 1.2 | 1.0 | 3.5 | 23.0 | 30.5 | 1291 | 84 |
3×25 | 10 | 1.4 | 1.2 | 4.0 | 28.0 | 35.5 | 1963 | 115 |
3×35 | 10 | 1.4 | 1.2 | 4.0 | 30.0 | 38.5 | 2438 | 142 |
3×50 | 16 | 1.6 | 1.2 | 5.0 | 36.0 | 46.0 | 3438 | 176 |
3×70 | 25 | 1.6 | 1.4 | 5.0 | 40.0 | 51.0 | 4465 | 224 |
3×95 | 35 | 1.8 | 1.4 | 5.0 | 44.0 | 55.0 | 5829 | 273 |
3×120 | 35 | 1.8 | 1.4 | 5.0 | 46.5 | 59.0 | 6627 | 316 |
3×150 | 50 | 2.0 | 1.6 | 5.0 | 52.0 | 66.0 | 7707 | 454 |