Medium Voltage Steel Wire Armored Power Cable

Medium Voltage Steel Wire Armored Power Cable

Introduction
Product Description
This product is suitable for rated voltage 3.6/6~26/35kV transmission and distribution lines.
Usage characteristics:
1. The maximum conductor temperature during normal operation is 90℃
2. The maximum short-circuit temperature of the conductor shall not exceed 250 ° C (5s maximum duration)
3. The ambient temperature shall not be lower than 0 ° C during cable laying
4. The bending radius of cable laying shall not be less than the following provisions:
Single core armoured cable: 15D
Three-core armored cable: 12D (D is cable diameter)
standard: GB/T 12706.2, GB/T 12706.3, IEC60502-2,IEC60502-3, DIN VDE 0276-620, NF C33-226, BS 6622
Rated voltage: 3.6/6~26/35kV
Technical parameter
 
Conductor Current - Carrying Capacity at 30° C* Short current circuit at 1 sec
Nom. Cross Sect.  (mm²) DC Resistance at 20°C Max. (Ω/km) AC Resistance at 90°C Max. (Ω/km)
inair Max. (A) in ground Max. (A) Conductor Max. (kA) Screen Max. (kA)
25 0.727 0.927 158 148 3.58 1.03
35 0.524 0.668 191 176 5.01 1.03
50 0.387 0.494 227 207 7.15 1.03
70 0.268 0.342 281 253 10.01 1.03
95 0.193 0.247 339 301 13.59 1.03
120 0.153 0.196 389 341 17.16 1.03
150 0.124 0.16 440 382 21.45 1.03
185 0.0991 0.128 501 430 26.46 1.37
240 0.0754 0.099 585 493 34.32 1.37
300 0.0601 0.08 663 551 42.9 1.37