Product Description
Aerial insulated cable have not only the power transmission characteristics of power cables, but also the strong mechanical characteristics of overhead cables. Compared with bare wires, overhead insulated cables have many advantages such as small laying span, high reliability, and good anti-aging performance.
1. Rated voltage U is 10kV
2. The cable laying temperature should not be lower than -20℃
3. Minimum bending radius: For single-core cables - 20(D+d)mm
Nominal cross-section mm^2 | Insulation Thickness mm | O.D. mm | Capacity μ F/km | Inductance mH/km | Approximate ampacity A | Appro.weight of product kg/km | |||
Soft copper | Copper | Aluminum | Copper | Aluminum | |||||
10 | 3.4 | 12 | 0.145 | 1.076 | 103 | 98 | 86 | 179 | 125 |
16 | 3.4 | 13.1 | 0.167 | 1.026 | 137 | 133 | 114 | 242 | 156 |
25 | 3.4 | 14.3 | 0.193 | 0.978 | 177 | 174 | 147 | 336 | 197 |
35 | 3.4 | 15.4 | 0.212 | 0.949 | 217 | 210 | 179 | 438 | 138 |
50 | 3.4 | 16.5 | 0.237 | 0.915 | 262 | 251 | 220 | 590 | 292 |
70 | 3.4 | 18.2 | 0.272 | 0.868 | 325 | 313 | 269 | 789 | 366 |
95 | 3.4 | 20.2 | 0.306 | 0.839 | 399 | 379 | 323 | 1039 | 465 |
120 | 3.4 | 21.7 | 0.333 | 0.817 | 446 | 441 | 376 | 1276 | 552 |
150 | 3.4 | 23.2 | 0.364 | 0.794 | 512 | 503 | 430 | 1556 | 642 |
185 | 3.4 | 25.2 | 0.394 | 0.774 | 589 | 583 | 495 | 1885 | 768 |
240 | 3.4 | 28.2 | 0.438 | 0.748 | 699 | 693 | 546 | 2392 | 960 |
300 | 3.4 | 29.8 | 0.468 | 0.725 | 809 | 808 | 608 | 2964 | 1139 |
400 | 3.4 | 33.2 | 0.568 | - | - | - | - | 3826 | 1449 |