THWN And THHN
Introduction
Application:
General purpose wiring in accordance with the National Electrical Code, maximum conductor temperature of 90°C in dry locations and 75°C in wet locations, 600 volts, for installation in conduit or other recognized raceway. Also used for wiring of machine tools (stranded), appliances, and control circuits not exceeding 600 volts.
Construction:
CU THHN/THWN(-2) conductors are made with soft drawn copper. Sizes 14 through 4/0 AWG use a combination-unilay stranding while 250 kcmil and larger sizes use a compressed copper stranding. The wire is covered with a tough heat and moisture resistant PVC insulation with an overall nylon jacket. Available in black, white, red, blue, purple, green, yellow, orange, brown, and gray. Some colors are subject to economic order quantity.
Standards: ASTMB3, ASTMB8, ASSTMB787, UL83, IEC60227
Technical parameter
UL83
IEC60227
THWN or THHN                                                                UL83                                                            
Size Conductor  Insulation Nylon Jacket Approx. weight
No.of Wires Dia. of wires Conductor Dia. Nominal Thickness Insulation Dia. Nominal Thickness Overall Dia.
AWG/kcmil No. mm mm mm mm mm mm kg/km
14 1 1.63 1.63 0.39 2.41 0.11 2.63 23.4
12 1 2.06 2.06 0.39 2.84 0.11 3.06 35.5
10 1 2.59 2.59 0.51 3.61 0.11 3.83 56
14 7 0.62 1.86 0.39 2.64 0.11 2.86 24.5
12 7 0.78 2.34 0.39 3.12 0.11 3.34 36.7
10 7 0.98 2.94 0.51 3.96 0.11 4.18 57.8
8 7 1.24 3.72 0.77 5.26 0.13 5.52 95.5
6 7 1.56 4.68 0.77 6.22 0.16 6.48 144
4 7 1.96 5.88 1.02 7.92 0.16 8.24 229.2
3 7 2.2 6.6 1.02 8.64 0.16 8.96 282.7
2 7 2.48 7.44 1.02 9.48 0.18 9.8 352.3
1 19 1.69 8.2 1.27 10.74 0.18 11.1 450.7
1/0 19 1.89 9.2 1.27 11.74 0.18 12.1 554.2
2/0 19 2.13 10.34 1.27 12.88 0.18 13.24 692.2
3/0 19 2.39 11.61 1.27 14.15 0.18 14.51 859.5
4/0 19 2.68 13.01 1.27 15.55 0.18 15.91 1067.5
250 37 2.09 14.2 1.53 17.26 0.21 17.68 1280.1
300 37 2.29 15.55 1.53 18.61 0.21 19.03 1521.9
350 37 2.47 16.79 1.53 19.85 0.21 20.27 1757.7
400 37 2.64 17.96 1.53 21.02 0.21 21.44 1996.1
500 37 2.95 20.05 1.53 23.11 0.21 23.53 2469.7
600 61 2.52 22 1.78 25.56 0.23 26.02 2994.7
750 61 2.82 24.64 1.78 28.2 0.23 28.66 3718.1
1000 61 3.25 28.4 1.78 31.96 0.23 32.42 4891.8
Section Insulation Thickness Sheath Thickness Overall Diameter Cable Weight Electrical Resistance
No.×mm² Class of conductor mm mm mm kg/km DC.20'C
0/km
2 ×0.75 1 0.6 0.9 4.6×7.1 38.5 24.5
2× 1.0 1 0.6 0.9 4.8×7.4 45 18.1
2 ×1.5 1 0.7 0.9 5.3×8.5 60 12.1
2 × 2.5 1 0.8 1 6.2×10.1 88.5 7.41
2 × 4.0 1 0.8 1 6.7×11.1 122.5 4.61
2×4 7 0.8 1 6.9×11.5 128 4.61
2×6 1 0.8 1.1 7.5×12.5 169 3.08
2×6 7 0.8 1.1 7.8×13 176 3.08
2×10 7 1 1.2 9.5×16.2 282 1.83
3×0.75 1 0.6 0.9 4.9×9.6 55 24.5
3×1 1 0.6 0.9 4.8×10.1 64 18.1
3×1.5 1 0.7 0.9 5.3×11.7 87 12.1
3×2.5 1 0.8 1 6.2×14 128 7.41
3×4 1 0.8 1 7×15.8 183 4.61
3×4 7 0.8 1 7.1×16.3 192 4.61
3×6 1 0.8 1.1 7.5×17.5 247 3.08
3×6 7 0.8 1.1 7.8×18.2 257 3.08
3×10 7 1 1.2 9.5×23 413 1.83
More other recommendations